| Plan Review Notes For Permit 03021272 |
| Permit Number |
03021272 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-04-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT A6 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT FLOOR PLAN. MASTER BATH HAS | | | 2 LAVS AND A SHOWER ON THE FLOOR PLAN | | | THAT DOES NOT APPEAR ON THE RISER DIA- | | | GRAM. - A CLEAN OUT IS REQUIRED ON WASH- | | | MACHINE STACK, MIN 4' ABOVE FINISHED | | | FLOOR. - TUB DRAINS SHALL TIE INTO BLDG | | | DRAIN AND BRANCH DRAIN BELOW SLAB NOT | | | ABOVE AS SHOWN. | | | 2) SHT A6 SANITARY RISER DIAGRAM, KIT- | | | CHEN SINK SHALL NOT DRAIN INTO THE WET | | | VENT OF THE BATHROOM GROUP. SEC 909.1 | | | BATHROOM GROUP SHALL BE TAKEN OFF SEPAR- | | | ATELY FROM BLDG. DRAIN. (SEE RED LINE | | | CORRECTIONS ON PLANS.) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|