Plan Review Notes
Plan Review Notes For Permit 03021272
Permit Number 03021272
Review Stop P
Sequence Number 2
Notes
Date Text
2003-04-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT A6 SANITARY RISER DIAGRAM DOES
 NOT REFLECT FLOOR PLAN. MASTER BATH HAS
 2 LAVS AND A SHOWER ON THE FLOOR PLAN
 THAT DOES NOT APPEAR ON THE RISER DIA-
 GRAM. - A CLEAN OUT IS REQUIRED ON WASH-
 MACHINE STACK, MIN 4' ABOVE FINISHED
 FLOOR. - TUB DRAINS SHALL TIE INTO BLDG
 DRAIN AND BRANCH DRAIN BELOW SLAB NOT
 ABOVE AS SHOWN.
 2) SHT A6 SANITARY RISER DIAGRAM, KIT-
 CHEN SINK SHALL NOT DRAIN INTO THE WET
 VENT OF THE BATHROOM GROUP. SEC 909.1
 BATHROOM GROUP SHALL BE TAKEN OFF SEPAR-
 ATELY FROM BLDG. DRAIN. (SEE RED LINE
 CORRECTIONS ON PLANS.)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692