| Notes |
| Date |
Text |
| 2003-04-09 00:00:00 | *********** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE FIRST SET OF REVIEW | | | NOTES, NOT ALL NOTES WERE ADDRESSED. | | | | | | 2)NOTE: PLEASE SEE MIN OCP FOR AHU @8KW | | | TO BE 125% 424-3. SHOWN AS 40A. | | | | | | 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED CIRCUITS ON PANEL SCHEDULE | | | PER 210-12 | | | | | | 4)NOTE: PLEASE CORRELATE RISER DIAGRAM | | | SHOWN ON A-6 AND PLANS. PLANS SHOW A | | | MAIN DISC OUTSIDE NEXT TO METER? | | | | | | 5)NOTE : PLEASE SHOW ALL GARAGE RECEPTS | | | PER 210-8 AS GFI.. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|