Plan Review Notes
Plan Review Notes For Permit 03021272
Permit Number 03021272
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-12 00:00:00************** UNSAT ***************
  
 1)NOTE : PLEASE SUBMIT AIC RATING FOR
 NEW SERVICE EQUIPMENT. MAINS/BRKRS/
 PANELS ARE ALL REQ`D TO BE RATED FOR THE
 AVAILABLE FAULT CURRENT. 110-9
  
 2)NOTE: PLEASE LIST THE REQ`D BATH
 CIRCUIT(S) PER 210-52D,210-11-C3
 20A/#12.
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 CIRCUITS PER 210-12
  
 4)NOTE: PLEASE SHOW ALL DISC`S REQ`D FOR
 EQIPMENT/AHU/WATER HEATER.
 440-11
  
 5)NOTE: PLEASE SIZE OCP FOR LOAD ON AHU.
 PLEASE SEE 424-3. MIN 125%
  
 6)NOTE: PLEASE SEE NFPA-72, 8-1.4.2
 MISSING SD`S INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS.
  
 7)NOTE: PLEASE SEE MISSING RECEPTS REQ`D
 PER 210-52.
  
 8)NOTE: PLEASE CHECK KITCHEN COUNTER-
 -SPACE FOR RECEPT SPACING PER 210-52-C1
  
 9)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 TO COLD WATER ALSO PER 250-50
  
 10)NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING PER 210-70 FROM GARAGE DOOR.
  
 11)NOTE: PLEASE SEE 210-8 FOR REQ`D
 GFI RECEPTS IN GARAGE.
  
 PLEASE COMPLETE PLANS PER NEC.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW