| Date |
Text |
| 2003-03-12 00:00:00 | ************** UNSAT *************** |
| | |
| | 1)NOTE : PLEASE SUBMIT AIC RATING FOR |
| | NEW SERVICE EQUIPMENT. MAINS/BRKRS/ |
| | PANELS ARE ALL REQ`D TO BE RATED FOR THE |
| | AVAILABLE FAULT CURRENT. 110-9 |
| | |
| | 2)NOTE: PLEASE LIST THE REQ`D BATH |
| | CIRCUIT(S) PER 210-52D,210-11-C3 |
| | 20A/#12. |
| | |
| | 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | CIRCUITS PER 210-12 |
| | |
| | 4)NOTE: PLEASE SHOW ALL DISC`S REQ`D FOR |
| | EQIPMENT/AHU/WATER HEATER. |
| | 440-11 |
| | |
| | 5)NOTE: PLEASE SIZE OCP FOR LOAD ON AHU. |
| | PLEASE SEE 424-3. MIN 125% |
| | |
| | 6)NOTE: PLEASE SEE NFPA-72, 8-1.4.2 |
| | MISSING SD`S INSIDE AND OUTSIDE ALL |
| | SLEEPING ROOMS. |
| | |
| | 7)NOTE: PLEASE SEE MISSING RECEPTS REQ`D |
| | PER 210-52. |
| | |
| | 8)NOTE: PLEASE CHECK KITCHEN COUNTER- |
| | -SPACE FOR RECEPT SPACING PER 210-52-C1 |
| | |
| | 9)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | TO COLD WATER ALSO PER 250-50 |
| | |
| | 10)NOTE: PLEASE SEE MISSING EGRESS |
| | LIGHTING PER 210-70 FROM GARAGE DOOR. |
| | |
| | 11)NOTE: PLEASE SEE 210-8 FOR REQ`D |
| | GFI RECEPTS IN GARAGE. |
| | |
| | PLEASE COMPLETE PLANS PER NEC. |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |