| Plan Review Notes For Permit 03021222 |
| Permit Number |
03021222 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-07 00:00:00 | **************** UNSAT ************* | | | | | | 1)NOTE: PLEASE CORRELATE OCP AND AWG | | | FOR AHU #2, SHOWS #10, W/ 60AOCP. | | | | | | 2)NOTE: PLEASE SUBMIT PANEL SCHEDULE | | | FOR MAIN. SHOWS EQUIPMENT BEING FED W/ | | | NO DETAIL FOR OCP ETC. | | | | | | 3)NOTE: PLEASE SEE MISSING RECEPT. | | | UPSTAIRS BR #4. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGH ELECTRICAL INSPECT- | | | -ION. IF THERE ARE ANY QUESTIONS , | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|