| Plan Review Notes For Permit 03021220 |
| Permit Number |
03021220 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-07 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT PANEL SCHEDULE | | | FOR MAIN PANEL. SHOWS ITEMS BEING FED | | | W/OUT ANY LISTINGS | | | | | | 2)NOTE: PLEASE CORRELATE OCP/AWG/KW | | | FOR AHU #2. SHOWS #10, 2P25AOCP W/ A | | | 10KW LOAD? | | | | | | 3)NOTE: PLEASE SEE LOAD CALCUALTIONS, | | | SHOWS 4 SM APPL, WASHER + 6KW. PLEASE | | | SEE LOAD @ 1500EACH SHOULD = 7500W. | | | | | | 4)NOTE: PLEASE ALSO SEE 4- SM APPL | | | LISTED IN LOAD CALCS AND ONLY 2 SHOWN | | | ON PANEL SCHEDULE. | | | | | | 5)NOTE: PLEASE SEE MISSING RECEPT IN | | | BR #4.210-52 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|