| Date |
Text |
| 2003-04-19 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | |
| | 1) ALL DEMO'D AND CAPPED PIPES SHALL BE |
| | INSPECTED PRIOR TO COVERING. |
| | 2) SHT P2.09A PLEASE IDENTIFY VALVES ON |
| | HOT WATER CIRCULATING LINE, NOT FOUND |
| | ON PLUMBING LEGEND - SHT P0.01 |
| | 3) SHTS P2.10B, P2.10C, & P5.04, OVER- |
| | FLOW DRAIN AT COL'S 18/U MINIMUM 8" REQD |
| | @ 2975 SQ FT. EXTEND CONNECTION TO 2ND |
| | OVERFLOW DRAIN AND INCREASE PIPE SIZE TO |
| | 8". TABLE 1106.3 - SECTION 1107.3 |
| | 4) SHT P2.10B 4" W & T AT CLASSROOM |
| | 1-350 APPEARS TO DRAIN TO 6" R.W.L. |
| | PLEASE CLAIRFY. PLEASE INDICATE WHAT |
| | THIS SYSTEM DRAINS. |
| | 5) SHTS P4.01 & P5.04 CONDENSATE SHALL |
| | DRAIN TO FLOOR SINKS. SECTION 803.2 |
| | HUB DRAINS NOT APPROVED. |
| | 6) SHTS P2.10CU & P5.01 ICE DISPENSORS |
| | #095895, & # 203201 SHALL DRAIN INDIREC- |
| | TLY INTO A FLOOR SINK. SECTION 802.3. |
| | 7) SHT P5.01 CLINICAL SINK, P-7A, PLEASE |
| | CLAIRFY IF THESE SINKS HAVE INTERNAL |
| | TRAPS OR NOT. NONE ARE SHOWN ON RISER. |
| | 8) SHTS P2.11 & P5.01 SINKS P20B SHOW |
| | 2" SANT ON FLOOR PLAN BUT 3" PIPE ON |
| | SANT. RISER. PLEASE CLAIRFY. |
| | 9) SHT P5.04 PHASE 10 PART B EXISTING 2" |
| | ROOF DRAIN. PLEASE PROVIDE SQ. FOOTAGE |
| | DRAINED BY THIS DRAIN PER SEC 1106. |
| | 10) SHT P5.04 - THE FOLLOWING INFORMAT- |
| | ION IS REQUIRED FOR GAS PERMIT. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. - PLEASE PROVIDE LENGTHS |
| | FOR SYSTEM AFTER REGULATOR. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED. |
| | C. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). PLEASE PROVIDE BTU'S ANTICIPAT- |
| | ED FOR FUTURE USE. |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | PLEASE INDICATE PRESSURE FOR SYSTEM |
| | AFTER REGULATOR. |
| | E. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | G) PLEASE INDICATE TABLE IN FBC-2001 |
| | FUEL GAS CODE THAT IS BEING USED TO |
| | SIZE PIPE FOR HIGH PRESSURE & MEDIUM |
| | PRESSURE SYSTEMS. |
| | 11) SHT P6.01 FILM PROCESOR DETAIL, PER |
| | SECTION 803.3 A FLOOR SINK WILL BE RE- |
| | QUIRED FOR INDIRECT WASTE. FLOOR DRAINS |
| | ARE NOT AN APPROVED RECEPTOR. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |