| Plan Review Notes For Permit 03021140 |
| Permit Number |
03021140 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-17 00:00:00 | PLEASE CLARIFY THE FOLLOWING INFORMATION | | | | | | 1.TEMPORARY CORRIDOR INDICATED ON PLAN | | | SHEET A0.10INDICATES THE DOORS ARE | | | 60 MIN. INDICATE WHAT PARTITION RATING | | | IS TO BE.WILL THIS BE UTILIZED DURNING | | | THE DEMO/RECONSTRUCTION OF PHASE 9 & 10? | | | FIRE OR FIRE SMOKE DAMPERS REQUIRED | | | WHILE THIS CORRIDOR IS IN USE. | | | | | | 2.PLEASE CLARIFY ALL SMOKE, FIRE OR | | | COMBINATION DAMPERS ON THE PLAN WHETHER | | | TEMPORARY OR PERMANENT. | | | | | | 3.MECH ROOM IN WHICH CH-3 IS TO BE | | | INSTALLED.VENTILATION, DETECTORS, | | | ALARMS, BREATHING APPERATUS OUTSIDE | | | ENTRANCE TO MECH RM TO BE BROUGHT UP TO | | | CODE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|