Plan Review Notes
Plan Review Notes For Permit 03021085
Permit Number 03021085
Review Stop E
Sequence Number 7
Notes
Date Text
2005-03-25 00:00:00PLANS REDLINED.
  
 METER/MAIN TO HAVE A 200A MAIN MAX.
 M/M IS 200A NOT 225A AS SHOWN ON RISER.
 SEC'S SHOWN AS 2/0'S, 200A MAIN MAX OCP.
 310.15B6, 240.4