2005-03-08 00:00:00********** UNSAT ****************
  
 1)NOTE: PLEASE SEE PLANS HAVE BEEN
 REDLINED SINCE THE BEGINING OF PROJECT
 FOR SEC'S AND SIZE OF EXISTING METER.
 PLEASE SEE 240.4,310.15B6 FOR MIN SIZE
 SEC'S FOR A 300A SERVICE.
  
 2)NOTE: PLEASE SEE 250.32 FOR GROUNDING
 AT DETACHED BLDG.S
  
 3)NOTE: PLEASE SEE LOAD CALCULATIONS
 HAVE NOW INCREASED FROM ORIGINAL 61A'S
 TO 91.6A'S
 PLEASE SUBMIT LOAD CALCULATIONS PER
 220.31B
  
 4)NOTE: PLEASE CLARIFY 3-SMALL APPLIANCE
 CIRCUITS FOR GARAGE?
  
 PLEASEBE SURE TO PLACE ON AS LITTLE
 PAGES AS POSSIBLE, AS REV' FEES ARE
 BASED ON $10 PER PAGE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  