Plan Review Notes
Plan Review Notes For Permit 03021085
Permit Number 03021085
Review Stop E
Sequence Number 2
Notes
Date Text
2004-04-17 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE LIST THE REQ'D BATH
 CIRCUIT ON PANEL SCHEDULE PER 210.52D,
 210.11C3
  
 2)NOTE: PLEASE SEE RISER INDICATES A
 300A SERVICE ON A 225A METERCAN. PLEASE
 VERIFY SIZING OF METERCAN.225A?
 PLEASE SEE SERVICE IS NOW ADDING A 100A
 DISC TO EXIST 200A SERVICE. PLEASE
 SEE 310.15B6 MIN CONDUCTOR SIZE FOR
 300A RESDENT SERVICE./ 230.42
  
 3)NOTE: PLEASE SEE 250.50 AND 250.32
 FOR NEW FOOTER STEEL AND COLD WATER
 AS PART OF THE GROUNDING SYSTEM AT
 DETACHED BLDG.
  
 4)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES A/C UNIT, BUT NONE SHOWN ON
 PLANS??
  
 PROVIDE LOAD CALCULATIONS 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]