| 2003-05-29 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT A1.0 UNABLE TO LOCATE SERVICE |
| | SINK INDICATED IN CODE ANALYSIS AND RE- |
| | VIEW "E". PLEASE INDICATE LOCATION. |
| | SERVICE SINK USED TO MOP FLOORS AND |
| | GENERAL CLEAN-UP. |
| | 2) SHT A1.0 IF URNALS ARE PROVIDED THEN |
| | AT LEAST ONE SHALL COMPLY WITH 11-4.18. |
| | SUBMIT DETAILS THAT SHOW HEIGHT 11-4.18. |
| | 2, CLEAR FLOOR SPACE 11-4.18.3, FLUSH |
| | CONTROLS 11-4.18.4. |
| | 3) SHT A1.0 PLEASE SUBMIT DETAILS FOR |
| | SHOWER IN COMPLIANCE WITH 11-4.21 AND |
| | ALL SUBSECTIONS. 11-4.21.4 GRAB BARS, |
| | 11-4.21.5 CONTROLS, 11-4.21.6 SHOWER |
| | UNIT, & 11-4.21.7 CURBS. |
| | 4) SHT A1.0 SINKS IN ROOMS #141 & 143, |
| | SHOW CLEAR FLOOR SPACE AS REQUIRED IN |
| | SECTION 11-4.24.5. |
| | 5) SHTS P-1, P-2, & P-3 RELIEF VALVE |
| | DISCHARGE PIPE STILL SHOWS BEING TRAPPED |
| | SECTION 504.7.1 |
| | 6) PER FBC ADMINISTRATIVE CODE, CHAPTER |
| | 1 AND AMENDMENTS SECTION 104.2.1TWO OR |
| | MORE COPIES OF SPECIFICATIONS AND OF |
| | DRAWINGS DRAWN TO SCALE WITH SUFFICIEDN |
| | CLAIRTY AND DETAIL TO INDICATE THE NAT- |
| | URE AND CHARACTER OF THE WORK SHALL |
| | ACCOMPANY THE APPLICATION FOR PERMIT. |
| | SUCH INFORMATION SHALL BE SPECIFIC, AND |
| | THE TECHNICAL CODES SHALL NOT BE CITED |
| | AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| | AS A SUBSTITUTE FOR SPECIFIC INFORMATION |
| | |
| | REVIEW BY KEN STEVENS |