2003-05-13 00:00:00DENIED:
  
 REVISED PLAN INDICATES THE PENETRATION
 BETWEEN 132A & 131 HAS A 1 HR RATING.
 PLEASE PROVIDE FIRE DAMPER ON THE 20" X
 16" SUPPLY DUCT AND THE 18" X 16" RETURN
 DUCT.ALSO SUPPLY & RETURN DUCTS AT THE
 MENS RM (135).PLEASE NOTE AS PER
 2001 FBC(M) 607.1.3 #3. 1-4 EXCEPTIONS,
 DUCTS SHALL MEET ALL REQUIREMENTS IN
 ITEMS 1-4 UNDER ITEM 3.
  