| Plan Review Notes For Permit 03021082 |
| Permit Number |
03021082 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-13 00:00:00 | DENIED: | | | | | | REVISED PLAN INDICATES THE PENETRATION | | | BETWEEN 132A & 131 HAS A 1 HR RATING. | | | PLEASE PROVIDE FIRE DAMPER ON THE 20" X | | | 16" SUPPLY DUCT AND THE 18" X 16" RETURN | | | DUCT.ALSO SUPPLY & RETURN DUCTS AT THE | | | MENS RM (135).PLEASE NOTE AS PER | | | 2001 FBC(M) 607.1.3 #3. 1-4 EXCEPTIONS, | | | DUCTS SHALL MEET ALL REQUIREMENTS IN | | | ITEMS 1-4 UNDER ITEM 3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|