Text |
| 2003-03-11 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT A-1.0 UNABLE TO FIND DRINKING |
| | FOUNTAINS AND SERVICE SINK REFERED TO IN |
| | CODE REVIEW AND ANALYSIS"E". |
| | 2) SHT A-1.0 IF TOILET ROOM ARE PROVIDED |
| | THEN EACH PUBLIC AND COMMON USE TOILET |
| | ROOM SHALL COMPLY WITH 11-4.22. IF BATH- |
| | ING ARE PROVIDED, THEN EACH PUBLIC AND |
| | COMMON USE BATHROOM SHALL COMPLY WITH |
| | 11-4.23 - PLEASE SHOW DETAILS FOR EACH |
| | TOILET ROOM AND BATHROOM PER THESE SECT- |
| | IONS AND ALL SUBSECTIONS. |
| | 3) SHT A-1.0 IF TOILET STALLS ARE PRO- |
| | VIDED, THEN AT LEAST ON SHALL BE A |
| | STANDARD TOILET STALL COMPLYING WITH |
| | 11-4.17. SEC 11-4.22.4 |
| | 4) SHT A-1.0 IF URNALS ARE PROVIDED THEN |
| | AT LEAST ONE SHALL COMPLY WITH 11-4.18 |
| | AND ALL SUBSECTIONS. |
| | 5) SHT A-1.01 PLEASE SUBMIT DETAILS FOR |
| | SHOWER IN COMPLIANCE WITH 11-4.21 AND |
| | ALL SUBSECTIONS. |
| | 6) SHT A-1.0 ALL DOORS SHALL NOT SWING |
| | INTO THE CLEAR FLOOR SPACE OF ANY FIX- |
| | TURE. ALSO 5' TURNING CIRCLE SHALL BE |
| | UNOBSTRUCTED. |
| | 7) SHT A-1.0 SINKS IN ROOMS #141 & 143 |
| | SHALL COMPLY WITH 11-4.24 AND ALL SUB- |
| | SECTIONS. PLEASE PROVIDE DETAILS. |
| | 8) SHT P-1 RELIEF VENTS REQUIRED AS |
| | CONDENSATE LINES EXIT BLDG. - CONDENSATE |
| | SHALL DRAIN OUTSIDE BLDG SEPARATE FROM |
| | STORM. (SEE ROOM #134) PLEASE CLAIRFY. |
| | 9) SHT P-1 KEYNOTE #6. MANUF INFORMATION |
| | REQUIRED. |
| | 10) SHT P-2 WATER RISER DIAGRAM, WATER |
| | HAMMER ARRESTORS REQUIRED AT ICE MAKERS |
| | (REFRIDGERATORS) SEC 406.9 |
| | 11) SHTS P-1, P-2, & P-3 RELIEF VALVE |
| | (P/T) FROM WATER HEATER SHALL NOT BE |
| | TRAPPED. SEC 504.7.1 |
| | 12) SEPARATE PERMIT REQD FOR IRRIGATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |