2003-03-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-1.0 UNABLE TO FIND DRINKING
 FOUNTAINS AND SERVICE SINK REFERED TO IN
 CODE REVIEW AND ANALYSIS"E".
 2) SHT A-1.0 IF TOILET ROOM ARE PROVIDED
 THEN EACH PUBLIC AND COMMON USE TOILET
 ROOM SHALL COMPLY WITH 11-4.22. IF BATH-
 ING ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON USE BATHROOM SHALL COMPLY WITH
 11-4.23 - PLEASE SHOW DETAILS FOR EACH
 TOILET ROOM AND BATHROOM PER THESE SECT-
 IONS AND ALL SUBSECTIONS.
 3) SHT A-1.0 IF TOILET STALLS ARE PRO-
 VIDED, THEN AT LEAST ON SHALL BE A
 STANDARD TOILET STALL COMPLYING WITH
 11-4.17. SEC 11-4.22.4
 4) SHT A-1.0 IF URNALS ARE PROVIDED THEN
 AT LEAST ONE SHALL COMPLY WITH 11-4.18
 AND ALL SUBSECTIONS.
 5) SHT A-1.01 PLEASE SUBMIT DETAILS FOR
 SHOWER IN COMPLIANCE WITH 11-4.21 AND
 ALL SUBSECTIONS.
 6) SHT A-1.0 ALL DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE OF ANY FIX-
 TURE. ALSO 5' TURNING CIRCLE SHALL BE
 UNOBSTRUCTED.
 7) SHT A-1.0 SINKS IN ROOMS #141 & 143
 SHALL COMPLY WITH 11-4.24 AND ALL SUB-
 SECTIONS. PLEASE PROVIDE DETAILS.
 8) SHT P-1 RELIEF VENTS REQUIRED AS
 CONDENSATE LINES EXIT BLDG. - CONDENSATE
 SHALL DRAIN OUTSIDE BLDG SEPARATE FROM
 STORM. (SEE ROOM #134) PLEASE CLAIRFY.
 9) SHT P-1 KEYNOTE #6. MANUF INFORMATION
 REQUIRED.
 10) SHT P-2 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS REQUIRED AT ICE MAKERS
 (REFRIDGERATORS) SEC 406.9
 11) SHTS P-1, P-2, & P-3 RELIEF VALVE
 (P/T) FROM WATER HEATER SHALL NOT BE
 TRAPPED. SEC 504.7.1
 12) SEPARATE PERMIT REQD FOR IRRIGATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377