| Plan Review Notes For Permit 03021082 |
| Permit Number |
03021082 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-26 00:00:00 | 1) DOORS (140A & 140C) MUST COMPLY WITH | | | CHAPTER 7.2.1.4 OF NFPA 101 LIFE SAFETY | | | CODE 2000 EDITION. | | | | | | 2) BOARDROOM OCCUPANT LOAD MUST COMPLY | | | WITH CHAPTER 7.3.1.2 OF NFPA 101 LIFE | | | SAFETY CODE 2000 EDITION. | | | | | | 3) SEPARATE PLAN AND PERMIT ARE REQUIRED | | | FOR FIRE ALARM SYSTEM. | | | | | | 4) ADDITIONAL HORN/STROBE MAYBE NEEDED | | | IN HALL 150. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 835-2910 |
|