| Plan Review Notes For Permit 03021082 |
| Permit Number |
03021082 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-04 00:00:00 | *************** UNSAT **************** | | | | | | | | | 1)NOTE: PLAN E-1 SHOWS SECONDARY METHOD | | | OF FEEDING MDP. PLEASE SHOW ON RISER | | | THIS METHOD AS OPT. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATING FOR | | | NEW 800A MAIN DISC. 110-9 | | | | | | 3)NOTE: PLEASE SHOW LOAD CALCUALTIONS | | | AND SHOW ALL CONTINUOUS LOADS AT 125% | | | INCLUDING LIGHTING LOADS. 215-3/230-42 | | | ETC. | | | | | | | | | 4)NOTE: PLEASE SHOW FEEDER AND CONDUIT | | | SIZE FROM MAIN TO MDP. | | | | | | PLEASE ALSO SEE FIRE REVIEW COMMENTS | | | THAT WILL AFFECT ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|