2003-03-04 00:00:00*************** UNSAT ****************
  
  
 1)NOTE: PLAN E-1 SHOWS SECONDARY METHOD
 OF FEEDING MDP. PLEASE SHOW ON RISER
 THIS METHOD AS OPT.
  
 2)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW 800A MAIN DISC. 110-9
  
 3)NOTE: PLEASE SHOW LOAD CALCUALTIONS
 AND SHOW ALL CONTINUOUS LOADS AT 125%
 INCLUDING LIGHTING LOADS. 215-3/230-42
 ETC.
  
  
 4)NOTE: PLEASE SHOW FEEDER AND CONDUIT
 SIZE FROM MAIN TO MDP.
  
 PLEASE ALSO SEE FIRE REVIEW COMMENTS
 THAT WILL AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW