| Plan Review Notes For Permit 03021082 |
| Permit Number |
03021082 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-01 00:00:00 | THE EXIT ACCESS CORRIDOR SHOWN AS "HALL" | | | ON THE PLANS IS REQUIRED TO BE ONE HOUR | | | FIRE RATED IN ACCORDANCE WITH FBC | | | 704.2.4.PLEASE REVISE AS NECESSARY. | | | | | | PROVIDE A SPECIFIC FRAMING AND FASTENING | | | DETAIL FOR THE SUSPENDED LOBBY SOFFIT | | | SHOWN ON SHEET A1.3.SEE FBC 104.2. | | | | | | SHOW THE WIND PRESSURE FOR THE NEW | | | EXTERIOR WINDOWS AND STOREFRONT SYSTEM. | | | SEE FBC 1606.1.7 | | | | | | SOME OF THE DOORS SWINGING INTO THE | | | CORRIDOR IE; ROOM 140A AND 134, DO NOT | | | COMPLLY WITH FBC 1012.1.4. | | | | | | SHOW SAFETY GLASS FOR THE INTERIOR | | | GLAZING ADJACENT TO THE DOORS AS | | | PROVIDED FOR IN FBC 2405.2.1 #3. |
|