| Date |
Text |
| 2003-02-27 00:00:00 | **********CORRECTIONS************ |
| | |
| | 1.)PLEASE COMPLETE OWNER INFORMATION |
| | ON THE PERMIT APPLICATION. |
| | |
| | 2.)PROVIDE A WALL SECTION DETAIL |
| | FROM FOUNDATION THROUGH THE ROOF FOR THE |
| | PROPOSED WALL AS PER FBC 104.3.1.1. |
| | SHOW ALL DIMENSIONS.SHOW ALL PROPOSED |
| | INSULATION ON THE WALL SECTION DETAIL, |
| | AS WELL AS OTHER ELEMENTS INCLUDING |
| | ALL ATTACHMENTS. |
| | |
| | 3.)PROVIDE A DETAIL FOR THE PROPOSED |
| | NEW PATIO SLAB.INCLUDE A DETAIL FOR |
| | BONDING OF FRESH CONCRETE TO HARDENED |
| | CONCRETE AS PER FBC 1924.6.2. |
| | |
| | 4.)PROVIDE TWO COPIES OF THE PRODUCT |
| | APPROVAL FOR THE PROPOSED 6-PANEL |
| | METAL DOOR SHOWN ON THE PLAN. |
| | |
| | 5.)INDICATE DRYWALL ON FURRING TO |
| | BE INSTALLED ON EXISTING PATIO WALLS |
| | ON THE PLAN.IF DRYWALL IS BEING |
| | INSTALLED ON THE CEILING, INDICATE THAT |
| | ON THE WALL SECTION DETAIL. |
| | |
| | 6.)PROVIDE A WINDOW SCHEDULE.SHOW |
| | SIZES AND LOCATIONS OF ALL EGRESS |
| | WINDOWS. |
| | |
| | 7.)IF AIR CONDITIONING IS TO BE |
| | SUPPLIED TO THE ROOM BEING ENCLOSED, |
| | APPLY FOR A MECHANICAL PERMIT.THIS |
| | PERMIT MAY BE APPLIED FOR SEPARATELY |
| | FROM THIS BUILDING PERMIT OR MAY BE |
| | SUBMITTED WITH THIS APPLICATION.FOR |
| | THE MECHANICAL PERMIT YOU WOULD NEED |
| | A PLAN, FORM 600C (SHORT FORM ENERGY |
| | CALC) AND THE MAKE, MODEL AND BTU OF |
| | THE EXISTING AHU. |
| | |