| Plan Review Notes For Permit 03021015 |
| Permit Number |
03021015 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-03 00:00:00 | PER N. MELICK MANUFACTURE INFO | | | NOT REQUIRED FOR 1 & 2 FAMILY HOMES. | | | JULY 17, 2002 OFFICAL INTERPRETATION. | | | THE FIELD INSPECTOR SHALL VERIFY THE | | | INSTALLED EQUIPMENT INPUT DOES NOT EX- | | | CEED THE PIPE SIZING. | | | | | | | | | DRYER ROOM IS A CONFINED SPACE - 1,100 | | | CUBIC FEET REQUIRED FOR 22,000 BTU'S - | | | 569 CUBIC FEET PROVIDED - 2 OPENINGS | | | ARE REQUIRED PER SECTION 304.3.1 |
|