2003-04-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT A6 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS OR REFLECT
 THE FLOOR PLAN.
 2) LAUNDRY TRAY AND WASH MACHINE CAN NOT
 DRAIN INTO THE SAME STACK AS BATH #2 LAV
 THEY ARE NOT ON A COMMON WALL.
 3) WASH MACHINE SHALL DRAIN DOWNSTREAM
 FROM THE LAUNDRY TRAY NOT ABOVE. A CLEAN
 OUT IS REQUIRED ON THE LAUNDRY STACK MIN
 OF 4' AFF.
 4) TUBS IN MASTER BATH AND BATH #2 SHALL
 NOT BE TAKEN OFF ABOVE THE SLAB AS SHOWN
 5) SHOWERS IN MASTER BATH, BATH #3, AND
 CABANA BATH SHALL NOT BE TAKEN OFF ABOVE
 THE SLAB AS SHOWN.
 6) BIDET IN MASTER BATH SHALL NOT BE
 TAKEN OFF ABOVE THE SLAB AS SHOWN.
 7) SIZE ALL SECTIONS OF PIPE.
  