| Plan Review Notes For Permit 03021008 |
| Permit Number |
03021008 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-03-12 00:00:00 | DENIED:MECHANICAL PERMIT 03021011 | | | | | | 1.ENERGY CALCULATIONS INDICATE A 13 | | | SEER UNIT PLANS INDICATE TWO 12 SEER | | | UNITS. | | | | | | 2.ONLY ONE UNIT SUBMITTED UNDER THE | | | MANUAL J CALCULATIONS (TOTAL OF 47,726 | | | BTU'S), ENERGY CALCS INDICATE 80,000 | | | BTU'S.PLAN INDICATES 2 UNITS. | | | | | | PLEASE CORRECT AND RESUBMIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. | | | PLEASE NOTE, THIS WAS NOT A RESUB, PLANS | | | MECH PLANS WERE OVERLOOKED |
|