2003-03-12 00:00:00DENIED:MECHANICAL PERMIT 03021011
  
 1.ENERGY CALCULATIONS INDICATE A 13
 SEER UNIT PLANS INDICATE TWO 12 SEER
 UNITS.
  
 2.ONLY ONE UNIT SUBMITTED UNDER THE
 MANUAL J CALCULATIONS (TOTAL OF 47,726
 BTU'S), ENERGY CALCS INDICATE 80,000
 BTU'S.PLAN INDICATES 2 UNITS.
  
 PLEASE CORRECT AND RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.
 PLEASE NOTE, THIS WAS NOT A RESUB, PLANS
 MECH PLANS WERE OVERLOOKED