| Date |
Text |
| 2003-03-12 00:00:00 | DENIED |
| | |
| | 1) ONE HOUR FIRE RATED GLASS BLOCK IS |
| | REQUIRED IN THE WALL ON THE ZERO LOT |
| | LINE. INDICATE THIS ON THE PLANS. |
| | |
| | 2) THE GLASS BLOCK LOCATED WITHIN 3 FEET |
| | HORIZONTALLY OF THE TUB/SHOWER IS |
| | REQUIRED TO HAVE A MINIMUM UNIFORM FACE |
| | THICKNESS OF 0.25" PER FBC 2405.2.2(5). |
| | PLEASE INDICATE THIS ON PLAN. |
| | |
| | 3) WIRE MESH IS REQUIRED TO BE SUPPORTED |
| | ON APPROVED MATERIALS AT MAXIMUM 3 FEET |
| | ON CENTER PER FBC 1909.3. |
| | |
| | 4) THE WIRE LATH NOTES ON A6 ARE NOT |
| | CORRECT. HIGH RIB METAL LATH IS REQUIRED |
| | TO BE ATTACHED AT EACH RIB (4"OC) AND |
| | SHALL BE ATTACHED TO HORIZONTAL WOOD |
| | FRAMING MEMBERS WITH NAILS OR STAPLES |
| | PROVIDING AT LEAST 1-3/4" PENETRATION |
| | INTO FRAMING MEMBERS. SEE ASTM C 1063. |
| | |
| | 5) FBC 1707.4.4.2 REQUIRES WOOD BUCKS |
| | 1-1/2" THICK AND GREATER TO EXTEND TO |
| | THE INTERIOR FACE OF THE JAMB. PLEASE |
| | REVISE SWING DOOR BUCK DETAIL ON AS2. |
| | |
| | 6) SPECIFY THE REQUIRED EMBED DEPTH OF |
| | THE 1/2" J-BOLT FOR THE USP NFM |
| | CONNECTORS ON A5. |
| | |
| | 7) PROVIDE THE MANUFACTURER'S SPECS. AND |
| | UL LISTING INFORMATION FOR A ONE HOUR |
| | FIRE RATED GLASS BLOCK ASSEMBLY. |
| | |
| | 8) THE TRUSS LAYOUT IS REQUIRED TO BE |
| | SIGNED, SEALED AND DATED BY THE TRUSS |
| | ENGINEER. THE COVER SHEET FOR THE TRUSS |
| | DRAWINGS REQUIRES THE ORIGINAL SIGNATURE |
| | OF THE TRUSS ENGINEER. A SIGNATURE |
| | STAMP IS NOT ACCEPTABLE. FAC 61G15-35 |
| | |
| | 9) AN EGRESS EASEMENT IS REQUIRED ON THE |
| | ZERO LOT LINE SIDE OF THE STRUCTURE |
| | FROM THE EGRESS OPENING TO THE PUBLIC |
| | WAY. |
| | |
| | 10) SEVERAL TRUSS CONNECTORS LISTED ON |
| | A5 ARE NOT ADEQUATE FOR THE UPLIFT LOADS |
| | ON THE TRUSS DRAWINGS. TRUSSES H73, H81, |
| | H115, H95, H101, H113, ETC. PLEASE |
| | REVIEW THE REQUIRED UPLIFTS ON THE TRUSS |
| | DRAWINGS AND REVISE THE SPECIFIED |
| | CONNECTORS. |
| | NOTE: THE TRUSS PLANS ARE NO LONGER |
| | REQUIRED TO BE SUBMITTED FOR PLAN REVIEW |
| | THEY ARE REQUIRED TO BE GIVEN TO THE |
| | BUILDING INSPECTOR AT THE ROOF FRAMING |
| | INSPECTION. |
| | |
| | 11) THE KEY PLAN INDICATES OPENING #5 AT |
| | THE WRONG LOCATION. PLEASE CORRECT. |
| | |
| | 12) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR THE SINGLE OUTSWING DOOR |
| | WITH SIDELITES (FRONT DOOR). |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |