| Date |
Text |
| 2004-09-21 00:00:00 | ******** UNSAT *********** |
| | |
| | PLEASE SEE REVISIONS FOR SHEETS : |
| | E-1,5,8,E-8A-CU, E-9A-CU, E9-10. |
| | |
| | PLEASE SEE COMMENTS/REDLINESFROM PREV- |
| | -IOUS REVIEWS. |
| | |
| | 1)NOTE: PLEASE SEE "DETAIL #2" FOR |
| | COOKING EQUIPMENT. THIS SHOWS BOTH UNITS |
| | BEING CONNECTED TO A "J-BOX" WITH NO |
| | DISCONNECTING MEANS. PLEASE SEE SOME |
| | UNITS PANEL IS W/IN SITE, YET SOME ARE |
| | NOT. PLEASE SEE 422.30,31,33 ETC FOR |
| | REQUIRED MEANS OF DICONNECT. |
| | |
| | 2)NOTE: PLEASE ALSO SEE SAME "DETAIL #2" |
| | WHICH DOES NOT INDICATE ANY NEUTRAL |
| | CONDUCTOR AS REQUIRED UNDER 250.140. |
| | |
| | 3)NOTE: PLEASE SEE REVISION FOR RFI-323, |
| | WHICH HAS INCLUDED LTS AND SD'S ON ARC- |
| | -FAULT PROTECTED BRKRS.THIS IS OK, HOW- |
| | -EVER, NOTE FOR ARC FAULT PROTECTION |
| | "**" ONLY INDICATES RECEPTS. THIS APPEAR |
| | -S TO JUST BE A NOTE THAT HAS NOT BEEN |
| | REVISED YET? |
| | |
| | 4)NOTE: PLEASE SEE RESPONSE LETTER FROM |
| | FES DATED AUGUST 20, 2004 FROM MARVIN |
| | SANCHEZ. NOTE(RESPONSE) # 4 MENTIONS BLD |
| | DEPARTMENT COMMENTS: DINING RM RECEPTS |
| | HAS BEEN CHANGED TO ARC FAULT PROTECTION |
| | ??? PLEASE VERIFY COMMENT AND/OR WHERE/ |
| | WHY THIS CHANGE WAS MADE. DINING RM |
| | RECEPTS ARE NOT REQUIRED TO BE ARC FAULT |
| | PROTECTED, UNLESS SO DESIRED. |
| | |
| | PLEASE SEE OTHER COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |