| Permit Number |
03020961 |
|
| Review Stop |
B |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2003-11-20 00:00:00 | PASSED AS PER PREVIOUS NOTE | | 2003-10-21 00:00:00 | CAN ACCEPT A SIGNED AND SEALED LETTER | | | FROM THE ENGINEER OF RECORD. | | 2003-10-10 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | SUBMITTAL 10/8/03 FOR POST TENSION SLAB | | | SHOP DRAWINGS: | | | | | | 1) ALL STRUCTURAL SHOP DRAWINGS SHALL BE | | | REVIEWED AND STAMPED BY THE ENGINEER OF | | | RECORD BEFORE SUBMITTAL.THIS IS STILL | | | REQUIRED EVENTHOUGH THE ENGINEER OF | | | RECORD MAY HAVE ATTACHED A COMMENT/ | | | REVIEW LETTER TO THE SHOP DRAWINGS. |
|