| 2004-12-14 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | ALTERNATIVE PRODUCT APPROVAL SUBMITTED |
| | ON 12/14/04 FOR DOOR S1-2A, FIRST FLOOR |
| | STAIR 2 EXIT DISCHARGE DOOR TO |
| | EXTERIOR. |
| | |
| | 1) THE PRODUCT APPROVAL WAS BROUGHT IN |
| | AS A SUBMITTAL FOR ZERO FEE.IT IS IN |
| | FACT A REVISION AND A REVISION FEE OF |
| | $60 IS DUE. |
| | |
| | 2) FBC 1606.1WIND PRESSURES ON DOOR |
| | S1-2A.SHEET S-22, WIND TUNNEL |
| | ANALYSIS |
| | RESULTS, SHOWS A PEAK NEGATIVE PRESSURE |
| | OF -80 PSF, FOR THIS LOCATION ON THE |
| | BUILDING.THIS EXCEEDS THE -70 PSF |
| | DESIGN PRESSURE RATING GIVEN IN THE |
| | SUBMITTED INGERSOLL-RAND COMMERCIAL |
| | STEEL DOOR PRODUCT APPROVAL NOA# |
| | 02-712.01 AND IS THUS OUTSIDE THE SCOPE |
| | OF THE PRODUCT APPROVAL.THIS DOOR HAS |
| | NOT BEEN DEMONSTRATED AS SUITABLE FOR |
| | USE IN THIS LOCATION. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |