| Plan Review Notes For Permit 03020961 |
| Permit Number |
03020961 |
|
| Review Stop |
FIRE |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2004-05-26 00:00:00 | 1) SINCE THE BUILDING IS A HIGH-RISE | | | BUILDING, TWO FIRE DEPARTMENT | | | CONNECTIONS ARE REQUIRED. | | | | | | 2) SEVERAL PAGES WERE INSERTED | | | UPSIDE DOWN IN PLANS PACKET. | | | | | | 3) NO NON-APPROVED EQUIPMENT OR DEVICES | | | ARE ALLOWED IN THE STAIRTOWERS. | | | | | | 4) DUCT SMOKE DETECTORS WHEN ACTIVATED | | | SHALL CAUSE THE FIRE ALARM SYSTEM | | | TO ACTIVATE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|