| Plan Review Notes For Permit 03020961 |
| Permit Number |
03020961 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-17 00:00:00 | DENIED: | | | | | | 1.PLAN SHEET AC-1, EXHAUST FROM | | | BATHROOM & PARCEL RM. PENETRATING2 HR | | | WALL, NO FIRE DAMPER INDICATED. | | | | | | 2.COMMENT #4 FROM PREVIOUS REVIEW | | | WAS ANSWERED IN RESPONSE LETTER BUT NOT | | | CHANGED ON PLAN (AC-5 & AC-6 ELEV LOBBY) | | | PLAN INDICATES A FIRE DAMPER ONLY NOT | | | A COMBINATION DAMPER.PLEASE CORRECT. | | | | | | 3.SEE COMMENTS FROM PLUMBING ON | | | CALCULATIONS FOR COMBUSTION AIR. | | | | | | 4.CONDENSING UNIT STANDS ON THE ROOF | | | SHALL COMPLY WITH 2001 FBC 1511.7 FOR | | | THE DISTANCE BETWEEN THE ROOF SURFACE | | | & THE BOTTOM OF THE SUPPORT RAIL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|