| 2003-05-16 00:00:00 | 1) THE ONE FDC NOTED NEAR THE SOUTHEAST |
| | CORNER IS FACING THE WRONG DIRECTION. |
| | IT SHOULD EITHER FACE 15TH STREET OR |
| | NORTH FLAGLER DRIVE. THE CURRENT |
| | ARRANGEMENT WILL CAUSE THE HOSE TO KINK |
| | AND THUS REDUCE ITS EFFECTIVENESS. |
| | |
| | 2) WHAT PREVENTS A SINGLE FIRE INCIDENT |
| | IN THE PARTY ROOM FROM BLOCKING BOTH |
| | EXITS. |
| | |
| | 3) A SIGN IS REQUIRED AT ELEVATOR # 3 |
| | INDICATING IT IS STRETCHER USEABLE. |
| | |
| | 4) THE SECURITY FEATURES PLANNED FOR THE |
| | GARAGE STILL SEEM TO LEAVE THIS WRITER |
| | CONFUSED WITH REGARDS TO EXITING. PLEASE |
| | EXPLAIN HOW EXITING WILL WORK IN THE |
| | GARAGE WHEN SECURITY DEVICES ARE |
| | INSTALLED. |
| | |
| | 5) THE TRASH CHUTE EXHAUST ON THE ROOF |
| | MUST EXTEND AT LEAST THREE FEET ABOVE |
| | THE ROOF. |
| | |
| | 6) TACTILE SIGNAGE REQUIRED AT |
| | STAIRWELLS. |
| | |
| | 7) PLEASE EXPLAIN THE (4) 2 1/2 X 2 1/2 |
| | X 6" SIAMESE CONNECTION. HOW MANY |
| | SIAMESE CONNECTIONS ARE PROPOSED. THIS |
| | OFFICE WILL ONLY REQUIRED TWO OF THEM. |
| | |
| | 8) THE COMMERCIAL SPACES ARE TO BE FIRE |
| | SPRINKLER PROTECTED AT THE TIME THE |
| | BUILDING IS COMPLETED. |
| | |
| | 9) SEPARATE PLANS AND PERMIT REQUIRED |
| | FOR ABOVE GROUND FUEL TANK. |
| | |
| | 10) EXIT SIGN APPEARS TO BE MISSING |
| | ON SOUTH SIDE OF GUEST PARKING AREA. |
| | |
| | 11) EMERGENCY LIGHTING COULD NOT BE |
| | LOCATED IN THE FIRE PUMP ROOM. |
| | |
| | 12) ARE THERE ANY EMERGENCY LIGHTS |
| | PRESENT FOR STAIR # 3 AND 4. |
| | |
| | 13) THERE APPEARS TO BE ISSUES WITH |
| | FIRE RATED DOORS AND WALLS IN SOME |
| | LOCATIONS. PLEASE REVISE THE PLANS. |
| | |
| | 14) PLEASE ILLUSTRATE COMPLIANCE WITH |
| | FBC 412.5. THE DESIGN INTENT IS NOT |
| | CLEAR TO THIS WRITER AT TIME OF |
| | THIS REVIEW. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |
| | 835-2910 |