| Date |
Text |
| 2003-05-01 00:00:00 | ********* UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE E-1, THERE ARE FEEDER |
| | /CONDUIT NOTES FOR MAINS 1 ETC. NOTES |
| | MENTION SEE "NOTE 7&9?ON WHICH PAGE |
| | WOULD THIS BE? |
| | |
| | 2)NOTE: PLEASE SEE RISER DIAGRAM AND |
| | E-1. E-1 SEEMS TO SHOW MAIN #2 AS BUS |
| | STAB AND RISER SHOWS CONDUIT/FEEDERS? |
| | PLEASE CORRELAT/CLARIFY. |
| | |
| | 3)NOTE: PLEASE SEE E-1, SHOWS MULTIPLE |
| | LINES COMING FROM HDP, RISER ONLY SHOWS |
| | 2LINES COMING OUT AND GOING UP TO ROOF.? |
| | CONDUITS THAT APPEAR TO COME FROM XDP |
| | ON RISER DIAGRAM SEEM TO BE SHOWN COMING |
| | FROM HDP ON E-1? PLEASE CORRELATE. PANEL |
| | HB? ETC |
| | 4)NOTE: PLEASE SEE E-13, IT APPEARS TO |
| | SHOW FEEDERS FOR MAIN 3 COMING OVERHEAD. |
| | PLEASE NOTE, AS PER LOCAL AMENDMENTS, |
| | NO MORE THAN 8' OF UNPROTECTED CONDUCTOR |
| | -S ARE PERMITTED INTO BLDG. PLEASE SHOW |
| | AS EITHER UNDERGROUND OR COMPLETE CONCR- |
| | -ETE ENCASEMENT. 230-70 LOCAL AMEND. |
| | |
| | 5)NOTE: PLEASE CLARIFY FIXTURE TYPE FOR |
| | ELEVATOR EQUIPMENT ROOM AND OTHER ROOMS |
| | THAT REQUIRE EMERGENCY LIGHTING REQ`D TO |
| | MEET 700-16? SOME OTHER LOCATIONS SHOW |
| | ROOMS AND TYPE OF FIXTURES REFERENCE |
| | BACK TO FIXTURE SCHEDULE.FIX SCH, DETAIL |
| | -S DUAL BALLAST/BULBS. |
| | |
| | 6)NOTE: PLEASE SEE E-8, SHOWS RECEPT |
| | ADDED TO SERVE KITCHEN COUNTER PENINSUL- |
| | -AR. HOWEVER SHOWN ON LIVING ROOM CIR- |
| | -CUIT? PLEASE SEE 210-11,210-52 220-16 |
| | ETC. MUST BE ON W/SMALL APPLAIANCE."A-3" |
| | PLEASE ALSO CLARIFY HOW THE CIRCUIT #`S |
| | ARE SHOWN AS THE SAME W/ AN A&B? |
| | |
| | 7)NOTE: PLEASE NOTE, OCP FOR FIRE PUMP |
| | TO BE PER 695-4B-1 ALSO SEE NOTE 12 |
| | |
| | 8)NOTE: PLEASE CLARIFY SIZE OF MAIN 4OF4 |
| | FEEDS 1000A PANEL AC ON ROOF. |
| | |
| | 9)NOTE: PLEASE CORRELATE FEEDERS NOTED |
| | ON BOTTOM OF LOAD CALCS FOR UNITS ON |
| | E-8,9,10 WITH RISER DIAGRAM. RISER SHOWS |
| | 3-#1'S ETC AND FEEDERS NOTED AT #2'S? |
| | |
| | 10)NOTE: PLEASE CLARIFY HOW POWER IS |
| | TRANSFERED OVER FROM FPL TO GENERATOR |
| | FOR FIRE PUMP? PLEASE ALSO SEE RISER |
| | DIAGRAM, SHOWS POWER FROM FPL TO EM MAIN |
| | AND THEN TO X-FER SWITCH, WHICH IS FINE, |
| | HOWEVER, SHOWS POWER COMING FROM |
| | GENERATOR TO EM MAIN? PLEASE CLARIFY HOW |
| | THE POWER WOULD BE TRANSFERED AT THIS |
| | LOCATION. HOW WOULD THIS KEEP POWER |
| | BEING ON EQUIPMENT AT THE SAME TIME |
| | FROM TWO DIFFERENT SOURCES W/OUT GOING |
| | THROUGH TRANSFER SWITCH? |
| | |
| | 11)NOTE: PLEASE SEE NOTE/WIRE/CONDUIT |
| | ON RISER DIAGRAM FOR FROM 1000A BRKR |
| | ON GENERATOR. |
| | |
| | 12)NOTE: PLEASE SHOW/CLARIFY MEANS OF |
| | DISC REQ`D FOR FIRE PUMP. PLEASE NOTE, |
| | SHOW A MANUAL MEANS REQ`D, 225-31 |
| | 230-76, 230-79, FOR DISC MEANS. |
| | PLEASE CLARIFY IF THERE WILL BE A MANUAL |
| | MEANS OF DISC AND/OR TRANSFER SWITCH |
| | LOCATED WITH/ON SERVICE ENTRANCE RATED |
| | EQUIPMENT/CONTROLLER FOR FIRE PUMP. |
| | |
| | 13)NOTE: PLEASE SEE GENERATOR NOTES, |
| | NOTES MENTION A 600A AND 400A BRKR ON |
| | GENERATOR AND ELECTRICAL RISER DIAGRAM |
| | EQUIPMENT NOTES, MENTION 500A AND 1000A |
| | OCP.? PLEASE CORRELATE. |
| | |
| | |
| | PLEASE NOTE, A RESPONSE LETTER FROM |
| | ELECTRICAL ENGINEER WILL HELP WITH |
| | CLARIFICATIONS OF SOME COMMENTS ETC. |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. IF A MEETING ON PHONE OR |
| | IN PERSON IS NEEDED, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |