| 2005-01-10 00:00:00 | REVISION - DENIED |
| | FOR SHEETS P-3, P-8, P-8, P-9, P-10, |
| | P-11, P-12, P-13, P-15, &P-16. |
| | |
| | 1) SHT P-3 NO CHANGES SHOWN FROM |
| | REVISION SEALED 07/29/04 AND REVIEWED ON |
| | 08/14/04. PLEASE CLAIRFY. SECTION |
| | 104.2.1. |
| | 2) SHT P-8 FLOOR SINK TO BE LOCATED SO |
| | PIPING FROM RVD SHALL NOT PRESENT A |
| | TRIPPING HAZARD. |
| | 3) SHTS P-9 & P-10 NO CHANGES SHOWN FROM |
| | ORIGINAL STAMPED SHEET SEALED 07/08/03 |
| | AND ISSUED 08/07/03. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | 4) SHTS P-11 & P-12 NO CHANGES SHOWN |
| | FROM REVISION SEALED 06/28/04, REVIEWED |
| | 08/14/04. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 5) SHT P-13 MANY RISERS SHOW REVISION |
| | NUMBERS 6 & 10 AND CLOUDED AT THE BASE |
| | OF THE RISERS, BUT NO CHANGES ARE SHOWN |
| | ARE SHOWN. PLEASE CLAIRFY. SECTION |
| | 104.2.1. - SANT. RISER #1, OFFSET VENT |
| | REQUIRED BETWEEN 5TH & 6TH FLOORS. |
| | SECTION 915.1. - SANT. RISER #17, |
| | HORIZONTAL DRY VENT NOT APPROVED. |
| | SECTION 905.3. |
| | 6) SHTS P-15 & P-16 NO CHANGES SHOWN |
| | FROM REVISION SEALED 08/20/04 AND |
| | REVIEWED 10/06/04. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | |
| | FOLLOWING SHEETS REVISIONS APPROVED. - |
| | P-2, P-5, P-6, P-9A-CU, P-10A-CU, P-17, |
| | & P-18 |
| | |
| | |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |