| 2003-03-15 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 11 |
| | FHA-AMEND 98 DESIGN MANUAL |
| | |
| | 1) SHT A5.1.05 DETAIL #1 EMPLOYEE REST- |
| | ROOM, DOOR CAN NOT OPEN INTO THE CLEAR |
| | FLOOR SPACE OF ANY FIXTURE OR THE 5' |
| | TURNING CIRCLE. 11-4.22.2. TURNING RADI- |
| | US SHALL BE UNOBSTURCTED. |
| | 2) SHT A5.1.08 UNIT BATHROOM INTERIOR |
| | ELEVATIONS, INDICATE OPENINGS FOR W/C'S |
| | AND LAV HEIGHTS PER FHA DESIGN MANUAL. |
| | 3) SHT A-7.1.0.6 ROOF DRAINS FOR CANOPY, |
| | PLEASE PROVIDE DRAIN DETAIL, PIPING |
| | DIAGRAM AND SHOW WHERE THE PIPING TERM- |
| | INATES. |
| | 4) SHT A-7.1.1.6 DETAIL #1 BREAKROOM |
| | ELEVATION, PER SECTION 11-4.24.2, MAX. |
| | HEIGHT FOR SINK SHALL BE 2'10". 2'11" |
| | SHOWN. |
| | 5) SHTS P-2 AND P-16, VENTS REQUIRED FOR |
| | FLOOR DRAINS IN PUMP ROOMS. |
| | 6) SHT P-2 MORE INFORMATION REQUIRED FOR |
| | DEEP STORAGE TANK IN TRANSFORMER VAULT. |
| | IS THERE ANY PIPING FOR THIS TANK? WHAT |
| | WILL BE STORED? |
| | 7) SHT P-2 NUMBER 4 IN BOX INDICATES A |
| | 3" SPRINKLER DRAIN, BUT WAS UNABLE TO |
| | LOCATE. THIS SHALL DRAIN TO SANITARY. |
| | PLEASE INDICATE WHERE THIS DRAIN IS. |
| | 8) SHT P-5 POOL EQUIPMENT ROOM SHOWS A |
| | 6" HUB DRAIN, BUT IS NOT SHOWN ON ANY |
| | RISER. PLEASE INDICATE WHAT THE DRAIN IS |
| | FOR AND WHERE IT PIPES TO. IF IT IS AN |
| | INDIRECT WASTE IT WILL REQUIRE A FLOOR |
| | SINK AND SHALL PIPE TO SANITARY. |
| | 9) SHT P-3 3" WATER FOR COOLING TOWER & |
| | 5" DOMESTIC WATER CHANGES ON SHT P-4, & |
| | CHANGES BACK ON SHT P-5. PLEASE CLAIRFY. |
| | 10) SHT P-6 SANITARY DRAIN LINES DO NOT |
| | REFLECT FIXTURE LAYOUT FOR PUBLIC BATH- |
| | ROOM DETAIL. |
| | 11) SHT P-8 WATER SUPPLY LINES FOR COOL- |
| | ING TOWER SHOWS 3" SUPPLY FROM PUMP, AND |
| | ANOTHER 3" LINE (#7) TYING INTO THE SYS- |
| | TEM. WHERE IS THIS LINE COMMING FROM. IS |
| | THIS A CROSS CONNECTION FROM THE DOMES- |
| | TIC WATER? PLEASE CLAIRFY. |
| | 12) SHTS P-9 UNIT A-1, & P-10 UNITS B-2A |
| | B-3, & B-2B, SECTION 909.1 WET VENT. |
| | ONLY THE FIXTURES WITHIN THE BATHROOM |
| | GROUP SHALL CONNEDT TO THE WET-VENTED |
| | HORIZONTAL BRANCH DRAIN. THE WASHMACHINE |
| | ON THESE STACKS SHALL DRAIN DOWNSTREAM |
| | OF THE BATHROOM GROUPS. ALSO MAKE CHANG- |
| | ES TO RISER DIAGRAM SHT P-13. |
| | 13) SHT P-12 WATER RISER DIAGRAMS (ALL). |
| | AIR CHAMBERS ARE NOT APPROVED. PLEASE |
| | DELETE THESE FROM THE RISER DIAGRAMS. |
| | 14) WATER RISER FOR PUBLIC BATHROOMS DO |
| | NOT REFLECT THE FIXTURE LAYOUT. NO WATER |
| | TO THE SHOWERS, DRINKING FOUNTAINS NOT |
| | SHOWN ON MENS, 4 LAVS IN WOMENS ROOM. |
| | PLEASE CLAIRFY. |
| | 15) SHT P-16 SANT. RISER TO PUBLIC BATHS |
| | DO NOT REFLECT THE FLOOR PLAN. |
| | 16) SHT P-16 PLEASE INDICATE PITCH FOR |
| | ALL SANITARY PIPE. ALL PIPE WILL BE RUN |
| | AT A UNIFORM PITCH. SIZING INDICATES |
| | 1/2" PER FOOT REQUIRED FOR SIZE OF PIPE |
| | AND NUMBER OF FIXTURES UNITS. |
| | 17) SHTS P-2 & P-16 CLEAN OUTS REQUIRED |
| | PER SECTION 708.3.1 IN THE BLDG DRAIN, |
| | MAX. 100', PER SECTION 708.3.4 AT CHANGE |
| | OF DIRECTION OVER 45 DEGREES, AND AT THE |
| | BASE OF EACH STACK PER 708.3.4. PLEASE |
| | SHOW C/O'S WHERE REQUIRED. |
| | 18) SHT P-13 SOIL AND WASTE STACKS IN |
| | BLDGS. HAVING MORE THAN 10 BRANCH INTER- |
| | VALS SHALL BE PROVIDED WITH A RELIEF |
| | VENT AT EACH 10TH INTERVAL INSTALLED BE- |
| | GINNING WITH THE TOP FLOOR. SEC 914.1 |
| | 19) PLEASE PROVIDE A HORIZONTAL CONDEN- |
| | SATE BLDG DRAIN LINE. SHOW ALL PIPE |
| | SIZES, POINT OF TERMINATION, AND SUPPLY |
| | CALCULATIONS FOR GALLONS PER MINUTE OF |
| | DISCHARGE FOR SYSTEM. SYSTEM SHALL RUN |
| | SEPARATELY OUT OF BLDG WITH A RELIEF |
| | VENT AS IS EXITS BLDG. |
| | 20) PLEASE PROVIDE A HORIZONTAL BLDG |
| | STORM DRAIN. SHOW ALL PIPE SIZES, PITCH, |
| | ACCUMULATED SQUARE FOOTAGE, AND TERMIN- |
| | ATION POING. |
| | 21) PLEASE PROVIDE A STORM RISER DIAGRAM |
| | SHOW ALL ROOF DRAIN SIZES, SQ FT DRAINED |
| | PIPE SIZE, PITCH, AREA DRAINS, AND |
| | PLANTER DRAINS WITH ACCUMULATED SQ FT. |
| | 22) HEALTH DEPT REVIEW REQUIRED FOR |
| | FACILITIES FOR POOLS. |
| | 23) SEPARATE PERMIT REQUIRED FOR POOLS. |
| | 24) A GREASE TRAP WILL PROBABLY BE REQ- |
| | UIRED IF ANY OF THE USES FOR THE RETAIL |
| | SPACE MENTIONED ON SHT G-4 THAT PREPARE |
| | OR SERVE FOOD ARE USED. IN THAT EVENT, |
| | PER UTILITY ORD #2938-96 RODNEY COMPO, |
| | ENVIRONMENTAL COMPLIANCE WILL BE CONTAC- |
| | TED FOR GREASE TRAP SIZE. (561) 837-4074 |
| | 25) SHT P-8 COOLING TOWER DRAIN TO SAN- |
| | ITARY AND OVER FLOW TO STORM. |
| | 26) SHT P-8 SHOWS 3" GAS LINE AT WATER |
| | HEATERS, BUT P-2 SHOWS ONLY 2" GAS AT |
| | METER. PLEASE CLAIRFY. |
| | 27) SEPARATE GAS PERMIT REQUIRED. THE |
| | FOLLOWING IS REQUIREMENTS FOR APPLYING. |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | 3. TYPE OF GAS, (LP OR NATURAL) |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | 6. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | 8. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | 10. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | 11. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | 28) SEPARATE PERMIT REQUIRED FOR GREASE |
| | TRAP. |
| | 29) SEPARATE PERMIT REQUIRED FOR IRRIGA- |
| | TION. |
| | 30) SHT P-2 PENETRATIONS INTO AND OPEN- |
| | INGS THROUGH A STAIRWAY ENCLOSURE ASSEM- |
| | BLY ARE PROHIBITED EXCEPT FOR REQUIRED |
| | EXIT DOORS, DUCTWORK AND EQUIPMENT NEC- |
| | ESSARY FOR INDEPENDENT STAIR PRESSUREIZ- |
| | ATION, SPRINKLER PIPING, STANDPIPES AND |
| | ELECTRICAL CONDUIT SERVING THE STAIRWAY |
| | AND TERMINATING ATY A STEEL BOX. - THE |
| | GAS LINE RUNNING THROUGH THE STAINWAY IS |
| | NOT ALLOWED.SECTION 1006.1.3.1 |
| | 30)........... |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |