| 2003-03-11 00:00:00 | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR REVIEW. |
| | |
| | 1.PROVIDE OUTSIDE AIR CALCULATIONS FOR |
| | THE COMMON AREAS, PER 2001 FBC(M) TABLE |
| | 403.3. |
| | |
| | 2.PROVIDE OUTSIDE A CALCULATIONS FOR |
| | THE RESIDENTIAL AREAS BY MEANS OF |
| | NATURAL VENTILATION (2001 FBC(M) 402.2) |
| | OR MECHANICAL (2001 FBC(M) TABLE 403.3). |
| | |
| | 3.SMOKE EVAC IS INDICATED FOR THE |
| | LOBBY & COMMON AREAS.INDICATE WHAT |
| | WILL BE DONE FOR THE CORRIDOR EXITS IN |
| | RESIDENTIAL AREAS.SHOW COMPLIANCE WITH |
| | 2001 FBC 412.5. |
| | |
| | 4.PLAN SHEETS AC-5 & AC-6 - SUPPLY |
| | PENETRATION AT ELEVATOR LOBBY INDICATES |
| | A FIRE DAMPER ONLY.PLEASE CLARIFY, |
| | SHOULD THIS BE A FIRE/SMOKE DAMPER? |
| | |
| | 5.PLAN SHEET AC-5 PENETRATION TO P/A 4 |
| | MISSING FIRE/SMOKE DAMPER ALSO. |
| | |
| | 6.MECHANICAL PLANS INDICATE IN-LINE |
| | BOOSTER FANS FOR THE DRYERS.PROVIDE |
| | SUBMITTAL FOR THE IN-LINE FAN.INDICATE |
| | IF ANY PRECAUTIONS ARE TO BE TAKEN |
| | SHOULD THE FAN FAIL (I.E. ALARM OR SOME |
| | TYPE OF NOTIFICATION). |
| | |
| | 7.PROVIDE ENERGY & MANUAL J CALCS AS |
| | PER 2001 FBC CHAPTER 13. |
| | |
| | 8.AS PER FAIR HOUSING GUIDELINES THE |
| | ENVIRONMENTAL CONTROLAS SHALL BE |
| | POSITIONED IN ACCESSIBLE LOCATIONS. |
| | HEIGHT REQUIREMENT SHALL BE A MINIMUM |
| | OF 15" A.F.F. & MAXIMUM OF 48" A.F.F.. |
| | |
| | 9.PROVIDE SEQUENCE OF OPERATION FOR |
| | ALL AREAS EVAC AS WELL AS SMOKE CONTROL. |
| | SHOW COMPLIANCE WITH 2001 FBC 412.5 |
| | |