| Date |
Text |
| 2003-02-20 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| | TO, DURING AND AFTER CONSTRUCTION. |
| | |
| | 2) SUITABLE ROADS ARE TO BE PROVIDED |
| | FOR FIRE AND PARAMEDICAL EQUIPMENT. |
| | |
| | 3) TEMPORARY STANDPIPES ARE REQUIRED |
| | WHEN THE BUILDING REACHES THREE STORIES |
| | OR THIRTY FEET IN HEIGHT. |
| | |
| | 4) ALL CONSTRUCTION, DEMOLITION, AND |
| | RENOVATION WORK TO COMPLY WITH NFPA |
| | 241. |
| | |
| | 5) ELECTRONIC TAMPER SWITCHES, A CHAIN |
| | AND LOCK ARE REQUIRED ON THE FIRE LINE |
| | BACKFLOW DEVICE. |
| | |
| | 6) A KNOX-BOX RAPID ENTRY SYSTEM WILL |
| | BE REQUIRED FOR THE BUILDING. |
| | |
| | 7) THE PARKING GARAGE IS TO BE SEPARATED |
| | BY AT LEAST A TWO HOUR FIRE RATING. |
| | |
| | 8) STAIR IDENTIFICATION SIGNS ARE |
| | REQUIRED. |
| | |
| | 9) ALL SHAFTS THAT ARE LARGE ENOUGH |
| | FOR PERSONS TO FALL INTO MUST BE MARKED |
| | "SHAFTWAY" IN RED LETTERS. |
| | |
| | 10) PLEASE REVIEW SECTION 412.4.3 OF |
| | THE FBC,"FIRE COMMAND CENTER", TO ENSURE |
| | ALL REQUIRED EQUIPMENT IS CONTAINED |
| | WITHIN. |
| | |
| | 11) QUICK RESPONSE OR LISTED |
| | RESIDENTIAL FIRE SPRINKLER HEADS ARE |
| | TO BE USED. |
| | |
| | 12) PLEASE INDICATE WHICH ELEVATORS |
| | COMPLY WITH THE FBC, SECTION 3003.4 |
| | "STRETCHER REQUIREMENTS". |
| | |
| | 13) PLEASE SHOW SIGNAGE "IN A FIRE |
| | EMERGENCY, DO NOT USE ELEVATOR". USE |
| | EXIT STAIRS" IN ACCORDANCE WITH FBC, |
| | SECTION 3003.3. |
| | |
| | 14) SHEET P-1 INDICATES A 6" FIRE LINE |
| | BUT OTHER SHEETS DISPLAY AN 8" LINE. |
| | IF THE FIRE PUMP IS 1000 GPM, THEN AN |
| | 8" LINE IS THE MINIMUM SIZE. PLEASE |
| | CORRECT DISCREPANCY. |
| | |
| | 15) PLEASE INDICATE ON THE PLANS, WHAT |
| | THE VOICE EVACUATION MESSAGE WILL SAY |
| | FOR THE FIRE ALARM SYSTEM. |
| | |
| | 16) THE BUILDING ADDRESS SIGN SHOWN ON |
| | A3.1.01 SHALL HAVE AT LEAST 6" NUMERALS. |
| | |
| | 17) PLEASE INDICATE COMPLIANCE WITH |
| | FBC,SECTION 412.5, "SMOKE CONTROL". |
| | |
| | 18) PLANS MAKE REFERENCE TO NFPA 13R. |
| | NFPA 13R IS NOT APPLICABLE TO THIS |
| | PROJECT. |
| | |
| | 19) SECURITY GATES SHOWN IN THE GARAGE. |
| | HOW DOES THESE DEVICES RESTRICT |
| | EXITING. |
| | |
| | 20) HOW DOES PERSONS EXIT VIA THE |
| | VEHICLE INGRESS AND EGRESS POINTS OF |
| | THE GARAGE. |
| | |
| | 21) INCOMPLETE LOCKING DEVICE NOTES ON |
| | PAGE LS1.02. |
| | |
| | 22) THE TWO EXITS SHOWN IN THE PARTY |
| | ROOM ARE NOT PROPERLY SEPARATED FROM |
| | ONE ANOTHER. |
| | |
| | 23) SEVERAL DOORS ON LEVEL 5 NEAR STAIR |
| | # 1 OPEN OUTWARD IN CLOSE PROXIMITY TO |
| | ONE ANOTHER. |
| | |
| | 24) SOME 20 MINUTE OR OTHER SYMBOLS |
| | ARE MISSING NEAR ELEVATOR LOBBY NEAR |
| | STAIR # 1. |
| | |
| | 25) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENTS FOR METAL GUARDRAILS |
| | MOUNTED ABOVE CRASH WALL. |
| | |
| | 26) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENTS FOR TEMPERED GLASS |
| | RAILING NOTED ON PAGE A1.1.05. |
| | |
| | 27) ALL RAMPS AND STAIRS TO HAVE |
| | HANDRAILS. |
| | |
| | 28) ALL FABRIC AWNINGS ARE TO BE FIRE |
| | RETARDANT. |
| | |
| | 29) DOOR SCHEDULE DIFFICULT TO READ. |
| | |
| | 30) AN EXIT SIGN APPEARS TO BE MISSING |
| | FROM GUEST PARKING. |
| | |
| | 31) PLEASE CLEARLY IDENTIFY ALL |
| | EMERGENCY LIGHTS. |
| | |
| | 32) ARE EMERGENCY LIGHTS PRESENT IN |
| | THE STAIRTOWERS. THE SYSMBOL USED DOES |
| | NOT SUGGEST THAT. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |
| | 835-2910 |