| Plan Review Notes For Permit 03020844 |
| Permit Number |
03020844 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-24 00:00:00 | 1) PLEASE SUBMIT FLOOR PLAN FOR EXITING | | | AND LIFE SAFETY. | | | | | | 2) PLEASE PROVIDE FLOOR PLAN DRAWING | | | INDICATING THE LOCATION OF ABOVE GROUND | | | TANKS TO BUILDING STRUCTURE AND PROPERTY | | | LINES. | | | | | | 3) NOTES ON PLAN REFERENCE NFPA 30 MUST | | | ALSO REFERENCE NFPA 88B. | | | | | | 4) PERMIT APPLICATION INDICATES 3 ABOVE | | | GROUND TANKS TO BE INSTALLED, PLAN ONLY | | | INDICATE 2 TANKS. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 835-2910 |
|