| Plan Review Notes For Permit 03020790 |
| Permit Number |
03020790 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-06 00:00:00 | ********* NOTES/PROVISO****** | | | | | | 1)NOTE: PLEASE CORRELATE OCP AND AWG | | | FOR AHU #2. SHOW 2P-60A ON#10. | | | | | | 2)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS | | | A EXT PANEL AND NO PANEL SCHEDULE IS | | | SUBMITTED. RISER SHOWS ITEMS FROM EXT | | | PANEL AND DOES NOT LIST ANY OCP . | | | | | | 3)NOTE: PLEASE SEE MISSING RECEPT | | | UPSTAIRS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGH INSPECTION. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|