| Date |
Text |
| 2003-03-05 00:00:00 | *************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SEE MISSING DISC REQ`D |
| | FOR A/C COND UNIT. 440-11 |
| | |
| | 2)NOTE: PLEASE SEE SIZE OF WIRE SHOWN |
| | FOR SUB PANEL, ON A 2P60A BRKR. PLEASE |
| | CORRELATE AWG W/ OCP. |
| | |
| | 3)NOTE: PLEASE ALSO SEE LOAD CALCULATION |
| | -S, FOR SUB PANEL, THEY DO NOT SEEM TO |
| | CORRELATE WITH WHAT IS SHOWN. PLEASE |
| | VERIFY LOADING OF 60A BRKR AT NO MORE |
| | THAN 80%? |
| | |
| | 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROTECTED CIRCUITS PER 210-12 |
| | |
| | 5)NOTE: PLEASE LIST THE REQ`D BATH |
| | CIRCUIT(S) PER 210-52D/210-11-C3. |
| | MUST BE 20A #12. SHOWN FOR GUEST HOUSE |
| | AS #14. 15A AND ALSO FOR MAIN HOUSE. |
| | |
| | 6)NOTE: PLEASE SEE RECEPT SPACING FOR |
| | KITCHEN COUNTERSPACE. PER 210-52-C-1 |
| | |
| | 7)NOTE: PLEASE SEE MAX OCP FOR COND UNIT |
| | SHOWN AS 5KW., SHOWS 2P50A BRKR? |
| | |
| | 8)NOTE: PLEASE SEE SMALL APPLIANCE |
| | CIRCUITS, SHOWS 2 CIRCUITS AND LOAD FOR |
| | THREE?? |
| | |
| | 9)NOTE: PLEASE SEE WRONG NEC ART REF. |
| | FROM 96 NEC, 250-95 SHOULD BE 250-122. |
| | |
| | 10)NOTE: PLEASE SEE ALL ROOM DESIGNATION |
| | -S ARE MISSING ON FLOOR PLAN? PLEASE |
| | SHOW. |
| | |
| | 11)NOTE: PLEASE MOVE SDIN GUESTHOUSE, |
| | TO BE IN IMEDIATE VICINITY OF STAIRS |
| | LEADING TO SECOND FLOOR. NFPA-72 |
| | 2-5.2.1.6 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |