| Plan Review Notes For Permit 03020682 |
| Permit Number |
03020682 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-03 00:00:00 | PLEASE CLARIFY THE FOLLOWING INFORMATION | | | | | | 1.CONDENSING UNIT SCHEDULE INDICATES | | | 11 SEER FOR C.U. #1A & 1B, ENERGY CACLS | | | SHOW A 11.5 SEER UNIT. | | | | | | 2.AHU SCHEDULE INDICATES 1995 CFM FOR | | | AHU #1, MANUAL J CALCS SHOW 2,221. | | | | | | 3.FAN SHUTDOWN REQUIRED AS PER 2001 | | | FBC(M) 606.2.1. | | | | | | 4.PLEASE NOTE, SHOULD GAS DRYER BE | | | INSTALLED, CHECK ROOM VOLUME FOR | | | CLASSIFICATION OF "CONFINED" (LESS THAN | | | 50 CUBIC FT PER 1,000 BTUS OF THE AGGRE- | | | GATE INPUT RATING OF ALL APPLIANCES | | | INSTALLED IN THAT SPACE).CONFINED | | | SPACES SHALL COMPLY WITH 2001 FBC(M) 703 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|