| Notes |
| Date |
Text |
| 2006-02-22 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE POWDER ROOM AND THE NEW POOL BATH | | | MUST HAVE RECEPTACLES PER 210.52(D), | | | PROTECTED PER 210.8(A)(1), ONA 20 AMP | | | CIRCUIT PER 210.11(C)(3). PLEASE INSERT | | | IN DRAWING AND CORRECT THE PANEL | | | SCHEDULE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|