2006-02-22 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE POWDER ROOM AND THE NEW POOL BATH
 MUST HAVE RECEPTACLES PER 210.52(D),
 PROTECTED PER 210.8(A)(1), ONA 20 AMP
 CIRCUIT PER 210.11(C)(3). PLEASE INSERT
 IN DRAWING AND CORRECT THE PANEL
 SCHEDULE.
  