| Plan Review Notes For Permit 03020560 |
| Permit Number |
03020560 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-28 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | 1} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 2} THE OVERCURRENT PROTECTION FOR THE | | | RANGE IS UNDERSIZED.( 10000/240=41.66 | | | AMPS.) | | | | | | PLEASE CORRECT THESE ITEMS BEFORE | | | CALLING INSPECTION. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT.8392 |
|