| Notes |
| Date |
Text |
| 2003-02-07 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | | GAS CODE SECTION 304. DRYER REQUIRES | | | 1,100 CU. FT. OF SPACE OR OPENINGS SHALL | | | BE REQUIRED PER SECTION 304.3.1. MIN. | | | 100 SQ. IN. OPENINGS. | | | 3. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|