2003-06-02 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 1} PLANS REFERENCE 1996 ELECTRICAL
 CODE,THESE PLANS WERE SUBMITTED UNDER
 THE 1999 CODE.
  
 2} THE PLANS REFERENCE ES-1 FOR FEED OF
 PANEL "H" TO "G-1" ES-1 SHOWS RISER FOR
 TRASH COMPACTOR.SHOW PANEL "H" AND FEED
 FOR "G-1".PLEASE REMOVE TRASH
 COMPACTORSHEET/RISER DIAGRAM.
  
 3} SHEET AME-1 NOTE ABOUT THE GROUND
 WIRE REFERENSES THE WRONG ELECTRICAL
 CODE AS WELL AS THE WRONG BUILDING
 CODE.PLEASE CORRECT.
  
 PLEASE MAKE THE ABOVE CHANGES AND
 RESUBMIT FOR REVIEW.
  