| Plan Review Notes For Permit 03020458 |
| Permit Number |
03020458 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-25 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | TO THE PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SIZE THE GROUNDING ELECTRODE | | | CONDUCTOR PER 250-66.(400 AMPS=400 MCM | | | PER 310-15(B)(6),400 MCM= 1/0 CU PER | | | 250-66) | | | | | | 2} PLEASE PROVIDE A PANEL SCHEDULE FOR | | | PANEL "B" AND SHOW LOCATION ON DRAWING. | | | | | | 3} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 4} THE LAUNDRY CIRCUIT IS INCORRECTLY | | | CALCULATED AT 1.0 KVA. THIS CIRCUIT IS | | | REQUIRED TO BE 1500 VA MINIMUM PER | | | 220-16(B). | | | | | | 5} PLEASE NOTE THAT SMOKE DETECTORS ARE | | | NOT TO BE LOCATED WITHIN 3'OF THE | | | KITCHEN PER 8-1.4.2 NFPA-72. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT.8392 |
|