Plan Review Notes
Plan Review Notes For Permit 03020458
Permit Number 03020458
Review Stop E
Sequence Number 1
Notes
Date Text
2003-02-25 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SIZE THE GROUNDING ELECTRODE
 CONDUCTOR PER 250-66.(400 AMPS=400 MCM
 PER 310-15(B)(6),400 MCM= 1/0 CU PER
 250-66)
  
 2} PLEASE PROVIDE A PANEL SCHEDULE FOR
 PANEL "B" AND SHOW LOCATION ON DRAWING.
  
 3} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 4} THE LAUNDRY CIRCUIT IS INCORRECTLY
 CALCULATED AT 1.0 KVA. THIS CIRCUIT IS
 REQUIRED TO BE 1500 VA MINIMUM PER
 220-16(B).
  
 5} PLEASE NOTE THAT SMOKE DETECTORS ARE
 NOT TO BE LOCATED WITHIN 3'OF THE
 KITCHEN PER 8-1.4.2 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392