| Plan Review Notes For Permit 03020452 |
| Permit Number |
03020452 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-26 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE LIST THE REQ`D BATH | | | CIRCUIT PER 210-52D/ 210-11-C-3 | | | 20A/#12 | | | | | | 2)NOTE: PLEASE SEE MIN SIZE FOR WASHER | | | PER 220-16B | | | | | | 3)NOTE: PLEASE SEE NFPA-72 8-1.4.2 | | | SD NOT PERMITTED IN KITCHEN. IF INSTALL- | | | ED, MUST BE A MIN OF 3' AWAY | | | | | | 4)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | | PER MIN SERVICE ENTRANCE CONDUCTORS | | | 250-66. SHOWN AS 400A SERVICE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|