2003-02-26 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE LIST THE REQ`D BATH
 CIRCUIT PER 210-52D/ 210-11-C-3
 20A/#12
  
 2)NOTE: PLEASE SEE MIN SIZE FOR WASHER
 PER 220-16B
  
 3)NOTE: PLEASE SEE NFPA-72 8-1.4.2
 SD NOT PERMITTED IN KITCHEN. IF INSTALL-
 ED, MUST BE A MIN OF 3' AWAY
  
 4)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 PER MIN SERVICE ENTRANCE CONDUCTORS
 250-66. SHOWN AS 400A SERVICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  