2004-02-12 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE SEE OCP SHOWN FOR 9KW
 AHU HEAT. SHOWN AT 45A'S, PLEASE VERIFY
 KW RATING AND PLEASE SEE 424.3B FOR
 MIN OCP TO BE 125%.
  
 2)NOTE: PLEASE SEE AHU, SHOWS A "J" BOX
 WHERE A DISC IS REQ'D PER 440.11.
 PLEASE INDICATE DISC MEANS.
  
 3)NOTE: PLEASE INDICATE CONDUCTORS FROM
 METER TO MAINS AND FROM MAIN TO PANEL.
 310.16
  
 4)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL.
 250.110,250.24, SIZE PER 250.122
 PLEASE ALSO INDICATE COLD WATER AS PART
 OF GROUNDING ELECTRODE SYSTEM. 250.50
 (IF METAL/COPPER).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  