| Plan Review Notes For Permit 03020451 |
| Permit Number |
03020451 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-25 00:00:00 | DENIED: | | | | | | 1.PLEASE REVISE OUTSIDE AIR CALCULATIONS | | | TO INCLUDE CHILD CARE ROOM. | | | | | | 2.PLAN SHEET AM-11 INDICATES 13 PERSONS | | | AND OUTSIDE AIR CALCULATIONS ONLY SHOW | | | 8 PEOPLE.PLEASE CLARIFY. | | | | | | 3.INDICATE WHAT WILL BE KEPT IN THE | | | STORAGE ROOMS. | | | | | | 4.CLOSETS CANNOT BE USED AS PLENUMS | | | WITH THE CONDENSATE OVERFLOW TERMINATING | | | IN THE AUXILIARY DRAIN PAN. | | | | | | 5.CONDENSATE SECONDARY DRAIN SHALL | | | TERMINATE AT A CONSPICUOUS POINT NOT | | | IN THE AUXILIARY DRAIN PAN. | | | | | | 6.PROVIDE SCHEDULE FOR EXHAUST FANS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|