Plan Review Notes
Plan Review Notes For Permit 03020451
Permit Number 03020451
Review Stop M
Sequence Number 1
Notes
Date Text
2003-02-25 00:00:00DENIED:
  
 1.PLEASE REVISE OUTSIDE AIR CALCULATIONS
 TO INCLUDE CHILD CARE ROOM.
  
 2.PLAN SHEET AM-11 INDICATES 13 PERSONS
 AND OUTSIDE AIR CALCULATIONS ONLY SHOW
 8 PEOPLE.PLEASE CLARIFY.
  
 3.INDICATE WHAT WILL BE KEPT IN THE
 STORAGE ROOMS.
  
 4.CLOSETS CANNOT BE USED AS PLENUMS
 WITH THE CONDENSATE OVERFLOW TERMINATING
 IN THE AUXILIARY DRAIN PAN.
  
 5.CONDENSATE SECONDARY DRAIN SHALL
 TERMINATE AT A CONSPICUOUS POINT NOT
 IN THE AUXILIARY DRAIN PAN.
  
 6.PROVIDE SCHEDULE FOR EXHAUST FANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.