| Plan Review Notes For Permit 03020451 |
| Permit Number |
03020451 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-11 00:00:00 | 1) ACCESS CONTROLLED EGRESS DOORS MUST | | | COMPLY WITH CH 7.2.1.6.2 OF NFPA 101 | | | LIFE SAFETY CODE 2000 EDITION. | | | | | | 2) PLEASE INDICATE AS TO WHAT WILL BE | | | STORED IN THE STORAGE ROOM. | | | | | | 3) SEPARATE PLAN AND PERMIT REQUIRED FOR | | | THE FIRE ALARM SYSTEM. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 835-2910 |
|