Plan Review Notes
Plan Review Notes For Permit 03020451
Permit Number 03020451
Review Stop B
Sequence Number 1
Notes
Date Text
2003-02-28 00:00:00PAID PLAN REVIEW NOT A PERMIT
 APPLICATION
  
  
 THE ATTIC ACCESS IS NOT SHOWN AS
 REQUIRED BY FBC 2309.6
  
 THIS BUILDING WILL BE LOCATED IN AN AO
 FLOOD ZONE.SHOW THE FINISH FLOOR
 REALTIVE TO NGVD 1929.
  
 HOW WERE THE WIND DESIGN PRESSURES
 DETERMINED?WAS THE BUILDING DESIGNED
 AS ENCLOSED OR PARTIALLY ENCLOSED?SEE
 FBC 1606.1.1 AND NOTE IF 1606.2, ASCE
 7-98 SECTION 6.5 WAS USED.
  
 HOW WAS THE ROOF TILE NAILING SPECIFIED
 ON SHEET AM 11 DETERMINED?SEE FBC
 1507.4 AND FBC 1606.3.2.
  