2003-05-20 00:00:00DENIED:LEASING OFFICE
  
 1.AIR HANDLER UNIT INSTALLATION DETAIL
 INDICATES THE SECONDARY DRAIN FROM THE
 EMERGENCY DRAIN PAN TIED INTO THE
 PRIMARY CONDENSATE DRAIN.AS PER 2001
 FBC(M) 307.2.3 & 307.2.4, SECONDARY
 DRAIN SHALL TERMINATE AT A CONSPICUOUS
 POINT TO SERVE AS AN ALARM THAT PRIMARY
 DRAIN RESTRICTED. A FLOAT SWITCH CAN BE
 USED IN PLACE OF A SECONDARY DRAIN.
  