| Plan Review Notes For Permit 03020450 |
| Permit Number |
03020450 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-05-20 00:00:00 | DENIED:LEASING OFFICE | | | | | | 1.AIR HANDLER UNIT INSTALLATION DETAIL | | | INDICATES THE SECONDARY DRAIN FROM THE | | | EMERGENCY DRAIN PAN TIED INTO THE | | | PRIMARY CONDENSATE DRAIN.AS PER 2001 | | | FBC(M) 307.2.3 & 307.2.4, SECONDARY | | | DRAIN SHALL TERMINATE AT A CONSPICUOUS | | | POINT TO SERVE AS AN ALARM THAT PRIMARY | | | DRAIN RESTRICTED. A FLOAT SWITCH CAN BE | | | USED IN PLACE OF A SECONDARY DRAIN. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|