| Plan Review Notes For Permit 03020450 |
| Permit Number |
03020450 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) AM-2 DRINKING FOUNTAIN REQUIRED PER | | | TABLE 403.1. ALSO SEE 410.1 | | | 2) SHT PM-1 WATER HEATER DETAIL, THERMAL | | | EXPANSION CONTROL REQUIRED. SEC 607.3.2 | | | T/P SHALL NOT BE TRAPPED. 504.7.1 | | | 3) SHT PM-1 WATER RISER DIAGRAM, (LABEL- | | | ED SANITARY RISER DIAGRAM), WATER HAMMER | | | ARRESTORS ARE REQUIRED AT DISHWASHER AND | | | ICE MAKER. SECTION 604.9 | | | 4) SHT PM-1 CONDENSATE TO SPILL MINIMUM | | | OF 12" FROM BLDG. SECTION 1503.4.4 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|