Plan Review Notes
Plan Review Notes For Permit 03020450
Permit Number 03020450
Review Stop P
Sequence Number 1
Notes
Date Text
2003-03-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) AM-2 DRINKING FOUNTAIN REQUIRED PER
 TABLE 403.1. ALSO SEE 410.1
 2) SHT PM-1 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL REQUIRED. SEC 607.3.2
 T/P SHALL NOT BE TRAPPED. 504.7.1
 3) SHT PM-1 WATER RISER DIAGRAM, (LABEL-
 ED SANITARY RISER DIAGRAM), WATER HAMMER
 ARRESTORS ARE REQUIRED AT DISHWASHER AND
 ICE MAKER. SECTION 604.9
 4) SHT PM-1 CONDENSATE TO SPILL MINIMUM
 OF 12" FROM BLDG. SECTION 1503.4.4
  
 REVIEW BY KEN STEVENS