2003-02-28 00:00:00PAID PLAN REVIEW NOT A PERMIT
 APPLICATION.
  
 THE ARCHITECT'S SHEET AM-6 LABELED
 FLOOR FRAMING PLAN WOULD SERVE BETTER
 AS THE ENGINEER'S SHEET AMS-2 LABELED
 ROOF FRAMING PLAN.
  
 SHEET AMS-3 CODES AND SPECS DECLARES ACI
 530-92.THE FBC INVOKES THE 1999
 EDITION, SEE FBC 3501.
  
 THE BUILDING WILL BE LOCATED IN A FLOOD
 ZONE AO, SHOW THE FINISH FLOOR
 ELEVATION RELATIVE TO NGVD 1929 ON THE
 PERMIT APPLICATION PLANS.
  
 SHOW AN ATTIC ACCESS IN ACCORDANCE WITH
 FBC 2309.6