| Plan Review Notes For Permit 03020431 |
| Permit Number |
03020431 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-11 00:00:00 | DENIED: | | | REFERENCE BUILDING PERMIT 01091426 | | | 1997 SBC.PLANS CALL FOR A 1 HR RATED | | | BECAUSE OF 3 STORY CONSTRUCTION. | | | MECHANICAL PLANS NEED TO REFLECT WHAT | | | PROTECTION IS BEING USED FOR THE | | | PENETRATIONS OF THESE RATED FLOORS, | | | CEILINGS ETC. (RADIATION DAMPERS AT | | | 1ST & 2ND FL LEVELS FIRE DAMPER AT | | | 3RD FL GRILLE?)PLEASE CLARIFY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|